0:03
click PLC and node red combined to make
0:05
a powerful automation system the
0:08
step-by-step guide teaches how to
0:09
install a PLC C2 n red module into the
0:13
click plus option slot we will cover the
0:16
basics of PLC module installation making
0:18
it perfect for beginners or those new to
0:22
plus get ready to upgrade your
0:24
automation system with ease node red is
0:27
a visual programming tool for connecting
0:29
phys physical Hardware devices apis and
0:32
online services as part of the Internet
0:34
of Things node Red's low code drag and
0:37
drop interface makes it easy to create
0:39
complex flows with minimum code whether
0:42
you're an Industrial Automation
0:44
professional or a DIY Enthusiast we will
0:47
walk you through installing the node red
0:48
PLC module in the click plus option slot
0:52
from preparation to installation we've
0:54
got you covered let's start now and take
0:56
your automation skills to the next level
1:00
detailed information contained in this
1:01
video can be found at ACC
1:21
The Click plus family of controllers now
1:24
has an intelligent options slot module
1:26
that combines time tested click hardware
1:28
with a popular node red open source tool
1:31
that has already been installed node red
1:33
has an extensive library of built-in
1:35
nodes for various tasks including input
1:38
output data processing logic and social
1:42
functions the c2n red module has an
1:45
independent processor ensuring the main
1:48
CPU of the click remains unburdened but
1:50
has direct access to the memory of the
1:52
PLC and all the data exchanges needed to
1:54
create a working application
1:57
easily you can even determine which
1:59
controller PLC or C2 and red or both
2:02
will control the process and several
2:04
node red nodes are available for working
2:07
specifically with the click plus
2:11
PLC download and install click PLC
2:14
programming software version
2:18
3.70 our click C2 and red module will
2:22
operate with click PLC programming
2:24
version 3.70 higher download the
2:27
software from the automation direct
2:30
unzip the file by right clicking and
2:45
all double click on a setup.exe file to
2:48
start the installation
2:53
process an information window will
2:55
appear asking you to disable antiv virus
2:57
sofware before proceeding select okay
3:00
okay the licensing agreement must be
3:03
accepted before you can continue the
3:04
installation of the click PLC
3:05
programming software select I accept
3:08
terms of the license agreement select
3:11
next you will be given the choice of
3:13
where to install the software on your
3:15
computer hit the change button to modify
3:18
or use the default display and select
3:21
next the ready to install message will
3:23
now be displayed select next to start
3:39
when the setup type is displayed select
3:41
create a desktop icon launch USB driver
3:45
installation and launch C2 intelligent
3:48
USB driver installer select
3:53
next the USB drivers will be checked and
3:56
updated if required maintaining drivers
3:58
to ensure that your soof is up the date
4:17
idea click the Finish button when the
4:19
click PLC programming software has
4:24
installed double click the icon on the
4:26
desktop to start the new version of our
4:28
click PLC programming software
4:31
Ware we will be showing the latest
4:33
features of this new software click next
4:36
additional new features and improvements
4:38
will be displayed click next software
4:41
and firmware fixes will now give you
4:43
insight into the software
4:45
package select don't display this
4:47
dialogue next time select it from the
4:50
main menu if you want to see this again
5:00
update the click plus PLC
5:05
firmware if you update from a click PLC
5:08
programing software version less than
5:10
3.07 like we are ensure that the C2 no
5:13
red module is not installed into the
5:17
controller we will connect to our
5:19
existing controller this could be done
5:20
using the connect icon on the main
5:22
screen or the connect to PLC selection
5:25
menu under the port type select ethernet
5:34
select refresh to have the software
5:36
check the network select connect to
5:38
communicate with the click PLC
5:46
network we will read the project from
5:51
okay the software will recognize that
5:53
the connect PLC has been programmed with
5:55
a different version and prompt you to
5:56
make a copy of the original click PLC
5:59
program select yes we can then name this
6:01
project or use the default and select
6:04
save we are now communicating with our
6:14
PLC select update firmware under the
6:31
the update firmware window will be
6:32
displayed under the CPU you will see
6:35
that we will be updating from version
6:38
3.70 ensure that the mode switch on the
6:44
update since we have already saved the
6:47
program in the PLC we can install the
6:49
new firmware without making a backup
6:51
copy of the click program select
6:55
okay select yes when asked to
6:58
update our click plus PLC CPU firmware
7:01
will be updated we can do this without
7:04
the node red module because the older
7:06
version does not have the existing
7:07
software for this intelligent module
7:34
a success message will be displayed when
7:36
the click PLC CPU firmware has been
7:39
updated select okay we can see that the
7:42
CPU firmware version has been updated to
7:45
3.70 close the update firmware window
7:49
select the disconnect button on the Home
7:50
tab of the click programming software
8:01
install the C2 node red click plus slot
8:05
module ensure the CPU controller is
8:08
powered off when installing modules and
8:10
PLC cards from The Click or click plus
8:13
PLC remove the option card cover if
8:16
installed by grasping its top and bottom
8:18
front edges squeezing and pulling it
8:20
Forward hold the option module by the
8:23
top and bottom front edges align the
8:25
card with the guide slot on the CPU and
8:27
Slide the module into its slot
8:30
press the module into place until it
8:32
seated push the top and bottom locking
8:35
Clips slightly backwards until they
8:38
place to remove the option module card
8:41
slightly lift on the Locking colors
8:43
until they release then slide each clip
8:45
forward reversing the
8:50
procedure update the C2 n red module
8:56
firmware we can now update the firmware
8:58
on our node red click click card this
9:00
module runs independently of the PLC
9:02
scan and can share information on the
9:04
controller's communication bus power up
9:06
the click plus PLC and select connect in
9:10
software select the found PLC controller
9:13
on our Network and select a
9:15
connect the login window will appear
9:18
since we do not have a program in the
9:19
PLC enter click for the password and
9:23
okay we are communicating with the click
9:26
PLC with node red module in the slot
9:29
under the setup on the main menu select
9:31
user account setup we will ensure that
9:33
we disabled our password
9:39
requirement on the Home tab select write
9:42
project this will write our existing
9:53
PLC once the transfer is complete select
10:01
we will now update our C2 n red node red
10:04
module select PLC from our main Tab and
10:19
firmware our update firmware window will
10:21
be displayed under the slot zero heading
10:25
our c2n red module will show that our
10:28
firmware needs to be updated
10:31
update a caution message is displayed
10:33
indicating that any program in our node
10:35
red module will be deleted select yes
10:38
there are two methods for updating our
10:40
C2 intelligent modules USB and ethernet
10:43
in our case we will connect to an
10:45
ethernet cable to our C2 and red
10:56
next select the ethernet option for C2
10:59
and red card and select connection
11:03
test select okay to acknowledge that the
11:08
next we can now review our firmware
11:14
start our firmware will now be updating
11:17
on our node red card do not remove power
11:20
to the PLC or computer during this
12:17
select okay once the firmware has been
12:18
updated successfully on your C2 n red
12:22
module select close to close the
12:26
window if you are enjoying this video
12:28
please hit the the like button below
12:30
keeping up with all the latest
12:31
automation Innovations can be difficult
12:33
so hit the Subscribe button remember to
12:35
hit the Bell beside your subscription to
12:37
actually receive those
12:42
notifications configuring the C2 and red
12:46
module enabling this click node red
12:49
module will allow it to function on the
12:51
setup tab of the main menu select slot
12:53
zero setting select C2 and red this will
12:57
call up the configuration window
13:01
select use the following IP address and
13:02
enter the static information you want to
13:04
use on your network we will also set up
13:09
addresses select the enable node red
13:11
option to ensure that we can use this
13:13
module we will leave the TCP port number
13:18
1880 all of the other items can be left
13:20
at the default settings you'll see that
13:23
URL address to view the programming of
13:25
our node red module select copy select
13:38
on the Home tab select WR project this
13:40
will write our configuration of the node
13:42
red module into the click Plus
13:48
controller select okay once the transfer
13:54
complete programming The Click plus PLC
14:01
module our module can now be programmed
14:04
to start and program our node red module
14:06
select open node red from the PLC tab of
14:10
menu select the ethernet option and
14:12
select connect your default browser will
14:15
open and you will see the node red
14:16
programming screen for the C2 and red
14:19
module another way to start the node red
14:22
interface is to start a new tab in the
14:23
browser and paste the URL address we
14:26
copied in the configuration
14:31
we will be first presented with a
14:33
welcome to node red 3.0 screen this will
14:36
take us through a series of screens
14:37
about the version of the node
14:39
red the latest version of node red is
14:41
4.0 but this release is compatible with
14:44
the click plus module
14:46
Hardware the nodes already pre-installed
14:48
in the click node red module are on the
14:50
screen's left side the right side of the
14:53
screen will show information on the
14:54
current configuration help files debug
14:59
programs will be written in flows in the
15:04
screen to learn more about node red
15:06
programming click here to see our
15:08
series click here to learn more about